5 sections, 17 items
1Identification
- Yes / no
Door reference and location confirmed against the label *
- Pass / fail
Certification label or plug present (top or hinge edge) *
No evidence the door is a certified fire door is itself a finding.
- Photo
Photo of the certification label
2Gaps and seals
- Pass / fail
Gap between door and frame consistent, typically 2 to 4 mm at head and sides *
Check the manufacturer's specification for the exact tolerance.
- Pass / fail
Threshold gap within specification (typically up to 8 mm, less with a smoke seal) *
- Pass / fail
Intumescent strips and cold smoke seals continuous, undamaged and not painted over *
3Door leaf and frame
- Pass / fail
Leaf free of damage, warping, holes or unfilled fixings *
- Pass / fail
Frame secure and undamaged, no gaps to the wall *
- Pass / fail
Glazing intact, fire-rated and beading secure
Mark not applicable if the door has no vision panel.
4Hardware
- Pass / fail
Hinges: at least three, CE or UKCA marked, all screws present and tight, no leaking oil *
- Pass / fail
Self-closing device closes the door fully into the frame from any angle, including from 75 mm open *
- Pass / fail
Latch engages and holds the door closed *
- Pass / fail
Hold-open devices, if fitted, release on the alarm
5Signage and use
- Pass / fail
Correct signage fitted (Fire door keep shut / keep locked / automatic fire door keep clear) *
- Pass / fail
Door not wedged or propped open, no obstructions on either side *
- Text
Notes on any defect found
- Signature
Inspector signature *
* Required